DEAERATORS
Guaranteed to Remove Oxygen in Boiler Feedwater to .005cc/liter

Available from 5,000 to 200,000 LBS/HR
The CRG deaerating boiler feedwater system eliminates the need of expensive oxygen scavenger chemicals and also offers the following advantages:

  • Removes carbon dioxide as well as oxygen.
  • Raises the boiler feedwater temperature, eliminating thermal shock in boilers.
  • Improves overall boiler room efficiency.
  • Feedwater pumps are sized for each individual application - assuring total compatibility and optimum operation.
  • Vessels are ASME Code constructed for 50 psig.
  • Compact design means smaller boiler room requirements.

WHY DEAERATE?

The use of deaerators has long been used in power plants and water tube type boilers, primarily because they remove undissolved oxygen and raise the temperature of the feedwater. These advantages are important today for firetube boilers as well, due to higher capital investments.

Operating costs can be reduced by recovering flash steam when returned by high temperature condensate. This feature also raises the feedwater temperature, thus requiring less boiler fuel to convert the feedwater to useable steam.

Boiler tubes, condensate lines, and process piping have a much longer useful life by eliminating the pitting action of untreated water. This advantage alone justifies the cost of a CRG deaerator.

HOW DOES IT WORK?

Undeaerated fresh water is fed into the deaerator through the inlet water connection. This water passes through the steam-filled heating and venting section. The water temperature is raised and many of the undissolved gases are released. As the water passes through the assembly, it flows to a scrubber section where final deaeration is accomplished by scrubbing the water with oxygen free steam. This steam is induced through a stainless steel spray valve assembly which causes the high velocity steam to break the water down to a fine mist through a violent scrubbing action. The deaerated water spills over to the tanks storage compartment for use by the boiler, and the gases are vented to the atmosphere.

STANDARD FEATURES :
  • Welded steel tank, designed and constructed for 50 psig as per the requirements of ASME Code; deaerating section with spray valve.
  • Structural steel stand with square tubing and steel pump platform.
  • Feedwater pump and motor sets, sized for each application.
  • Water inlet valve assembly for condensate return and fresh water.
  • Overflow trap, tank thermometer, pressure gauge.
  • Steam pressure reducing valve assembly with temperature controller.
  • Safety relief valve(s), vent valves, tank drain valve.
  • Water gauge glass set with cocks, drain valve, and protection rods.
    Pump suction piping with strainer and shutoff valve.
Deaerator Specifications
(all dimensions are in inches)
- DEAERATOR MODEL NO.  - - DA-5 DA-7 DA-10 DA-12 DA-14 DA-16 DA-19 DA-22 DA-26 -
- WEIGHT TANK/TRIM LBS 2400 2400 2700 2700 3000 3000 4000 4000 4500 -
- CAPACITY - LBS/HR 5,000 7,000 10,000 12,000 14,000 16,000 19,000 22,000 26,000 -
- WATER CAPACITY @ OVERFLOW GAL 268 268 331 331 456 456 789 789 957 -
- WATER CAPACITY @ NWL GAL 118 118 141 141 189 189 285 285 347 -
- WATER CAPACITY (W/DOME) FLOODED GAL 354 354 424 424 565 565 877 877 1033 -
A TANK DIAMETER - IN 42 42 42 42 42 42 48 48 48 A
B TANK LENGTH - IN 48 48 60 60 84 84 96 96 120 B
C OVERALL LENGTH BARE VESSEL IN 70 70 81 1/2 81 1/2 105 105 118 118 142 C
D SUPPORT STAND LENGTH - IN 46 46 54 54 72 72 84 84 96 D
E SADDLE WIDTH - IN 36 36 36 36 36 36 42 42 42 E
F STEAM INLET 150#-FLNG IN 4 4 4 4 6 6 6 6 6 F
G WATER OUTLET 150#-FLNG IN 3 3 3 3 4 4 4 4 6 G
H TANK DRAIN - IN 1 1/4 1 1/4 1 1/4 1 1/4 1 1/2 1 1/2 2 2 2 H
I OVERFLOW - IN 1 1/4 1 1/4 1 1/2 1 1/2 1 1/2 1 1/2 2 2 2 I
J CONDENSATE RETURN - IN 2 2 2 2 2 1/2 2 1/2 3 3 3 J
K INLET WATER - IN 1 1/4 1 1/4 1 1/4 1 1/4 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 K
L DOME DIAMETER - IN 12 12 12 12 14 14 16 16 16 L
M STEAM PURGE VENT - IN 3/4 3/4 3/4 3/4 1 1 1 1 1 M
N TANK HEIGHT FROM SUPPORT IN 66 66 66 66 72 72 76 76 76 N
O BASE OF SADDLE TO C/L OF TANK - IN 27 27 27 27 29 29 30 30 30 O
P C/L TO OVERFLOW - IN 7 1/2 7 1/2 9 9 9 9 9 1/2 9 1/2 9 1/2 P
Q HD. TO VENT CONNECTION - IN 24 24 30 30 42 42 48 48 60 Q
- DEAERATOR MODEL NO. - - DA-5 DA-7 DA-10 DA-12 DA-14 DA-16 DA-19 DA-22 DA-26 -
- DEAERATOR MODEL NO.  - - DA-30 DA-35 DA-40 DA-50 DA-60 DA-80 DA-100 DA-125 DA-150 DA-200 -
WEIGHT TANK/TRIM LBS 4500 4750 5700 7300 8000 8800 9500 10500 11500 14000 -
CAPACITY - LBS/HR 30,000 35,000 40,000 50,000 60,000 80,000 100,000 125,000 150,000 200,000 -
WATER CAPACITY @ OVERFLOW GAL 957 1025 1224 1600 1931 2421 2717 3810 4354 5796 -
WATER CAPACITY @ NWL GAL 347 365 444 560 679 848 954 1324 1517 1998 -
WATER CAPACITY (W/DOME) FLOODED GAL 1033 1091 1305 1673 2022 2521 2832 3935 4499 5956 -
A TANK DIAMETER - IN 48 54 54 66 66 72 72 84 84 96 A
B TANK LENGTH - IN 120 96 120 96 120 126 144 144 168 168 B
C OVERALL LENGTH BARE VESSEL IN 142 123 1/2 147 1/2 126 1/4 148 1/4 156 174 179 203 207 C
D SUPPORT STAND LENGTH - IN 96 84 102 84 108 108 120 132 128 132 D
E SADDLE WIDTH - IN 42 48 48 56 56 60 60 66 66 78 E
F STEAM INLET 150#-FLNG IN 6 6 6 8 8 10 10 10 10 10 F
G WATER OUTLET 150#-FLNG IN 6 6 6 6 6 6 6 8 8 8 G
H TANK DRAIN - IN 2 2 2 2 2 1/2 2 1/2 2 1/2 2 1/2 3 2 1/2 H
I OVERFLOW - IN 2 2 2 3 3 3 3 3 3 6 I
J CONDENSATE RETURN - IN 3 3 3 4 4 4 4 6 6 6 J
K INLET WATER - IN 1 1/2 2 2 2 2 2 2 2 1/2 2 1/2 4 K
L DOME DIAMETER - IN 16 18 18 20 20 20 20 24 24 30 L
M STEAM PURGE VENT - IN 1 1 1 1 1 1 1 1 1 1 M
N TANK HEIGHT FROM SUPPORT IN 76 86 86 101 101 111 111 124 124 135 N
O BASE OF SADDLE TO C/L OF TANK - IN 30 35 35 41 41 44 44 50 50 56 O
P C/L TO OVERFLOW - IN 9 1/2 11 3/4 11 3/4 16 16 16 16 17 17 24 P
Q HD. TO VENT CONNECTION - IN 60 51 60 48 60 60 72 72 84 84 Q
- DEAERATOR MODEL NO.  - - DA-30 DA-35 DA-40 DA-50 DA-60 DA-80 DA-100 DA-125 DA-150 DA-200 -
NOTE: STAND HEIGHT IS DEPENDENT ON NPSH OF PUMP REQUIRED
CONSULT FACTORY FOR LARGER SIZES.